APU331L Low Frequency Online UPS 10-120KVA
Description
3Phase Input/3Phase Output (380V/400V/415V)
Model Number: APU331L
- Double-conversion technology
- EPO
- ECO
- Strong overload capacity
- Input surge protection
- LCD + LED display
- Intelligence fan speed regulation
- Flexible network monitoring and management
Application: Industrial application protection; Power protection for institution such as transportation, electricity, medical care; small data room,; communication network management center; office automation; Experimental instrument and equipment.
Phase: 3Phase Input/ 3phase Output
Type: On-line
Capacity: 10KVA/15KVA/20KVA/30KVA/40KVA/60KVA/80KVA/100KVA/120KVA
Input:
Phase: 3 Phase+ Neutral+ Ground
Rated voltage: 380/400/415/Vac
Input Voltage Range: 285~475Vac
Rated Frequency: 50/60Hz
Input Frequency Range: 45-65Hz
Soft start: 1-100%, 5 seconds
Bypass:
Phase: 3 Phase+ Neutral+ Ground
Voltage range: 380/400/415Vac ± 15%
Frequency range: 50/60Hz ±2% (±0.5%, ±1%, ±2%, ±3%, settable)
Output:
Phase: 3 Phase+ Neutral+ Ground
Rated voltage: 380/400/415/Vac
Voltage regulation: ±1% for balance load, ±3% for unbalanced load
Rated frequency: 50/60Hz
Frequency Precision: 50/60Hz ±0.005% (Battery mode)
Power factor: < 1% (linear mode)
THDu: ≤1% (linear load)
Dynamic Voltage Transient: < 1% (from 0 to 100% load)
Transient recovery time: < 10ms (±5%)
Invertor overload: 105%-110%, 60mins, 110%-120%, 10mins; > 150%,10s
Efficiency:92%
Protection: Output short circuit protection, current limiting protection
Transfer time: Normal mode to battery mode, 0ms
Display: color touch screen
IP class: IP20
Communication Interface: RS232, RS485, SNMP card, dry contact
Operation Temperature: 0~40°C
Humidity: 0~95%
Noise: ≤65dB@ 1m
Charging current: 10-60KVA (6-20A); 80-120KVA (6-50A)